![]() You might try adjusting your ADDM syntax to the following: I also read where it specifically states to read the register address -1 just as u/PLC_Matt suggested. I did verify that this device is accepting of the Modbus function codes available to us in the READ_VAR FB (FC1, FC2, FC3 & FC4). I Googled for the manual on your DMG800 and found a document where it talks about how they implement their device with Modbus. So I don't think it's an hardware problem. ![]() I have tried to test the VFD (from which I can read/write) with every port of the plc rack. I have tried to use a modbus master simulator to see if I can read from the Analyzer (start address 50, 2 words) and it works immediately. On PLC startup it returns 1 for like 10 seconds and then it changes to 7. The function READ_VAR returns always error code 7 on the Gest "communication report" byte. RECP = array long enough to save read values in it. = 0 (I saw that changing this parameter is useless) ![]() ![]() If I want to read, for example, the frequency from the DMG (which is linked to the NOC0401) I have to refer to address 50 and 2 words. I know that I have to use "0.0.3" for "pointing" to PLC and "0.1.0" for NOC0401. I have zero problems (for now ahaha) reading from and writing to the VFD. I have this M340 equipped with a NOC0401 (4 eth ports) which have to communicate with an ABB VFD (acs380) and with an Analyzer dmg800 equipped with an ethernet module (EXP 10 13). Hi guys! I hope some of you can help me solving this problem. ![]()